AKL series
Suitable spec & price for local by Made in Thailand.
Cooling Capacity (50 Hz) | : | 12.0~25.0kW |
Operating Ambient Temp. Range | : | 5~43℃(AKL3750A-V) 5~38℃(AKL5500A-V/ AKL7500A-V) |
Operating Liquid Temp. Range | : | 10~30℃ |
Control Precision | : | ±1.0℃ |
Specifications
| Model | AKL3750A-V | AKL5500A-V | AKL7500A-V | |||
| Performance | Compressor output (50Hz) | HP | 4.0 | 8.7 | 12.3 | |
| Cooling capacity (50Hz)*1 | kW | 12.0 | 20.0 | 25.0 | ||
| TR | 3.4 | 5.7 | 7.1 | |||
| BTU/h | 40,900 | 68,200 | 85,300 | |||
| Ambient Temp. Range | ℃ | 5~43 | 5~38 | |||
| Operating temperature range (Liquid temperature) | ℃ | 10~30 | ||||
| Control accuracy*4 | ±1.0℃ and lower | |||||
| Operating Water Pressure | Mpa | 0.10~0.50 | 0.28~0.50 | 0.10~0.50 | ||
| Operating flow rate | L/min | 20~70 | 68~120 | 70~150 | ||
| Power specification | Power source*2 | V(Hz) | Three-phase 380±10% (50) | |||
| Power consumption*1 | kW | 5.4 | 9.0 | 11.8 | ||
| Electric current*1 | A | 9.7 | 15.6 | 22.0 | ||
| Power capacity*3 | kVA | 8.1 | 12.4 | 18.0 | ||
| Operation control method | Hot Gas Bypass Control | |||||
| Equipment details | Compressor | Fully sealed scroll type | ||||
| Condenser | Fin and tube forced air cooling | |||||
| Heat exchanger | Construction | Plate type heat exchanger | ||||
| Material | SUS316 (Brazing Cu) | |||||
| Discharge pump | Construction | Multistage centrifugal immersion type | ||||
| Output | kW | 1.1 | 1.46 | 1.46 | ||
| Water tank capacity | L | Approx. 95 | Approx. 115 | Approx. 140 | ||
| Refrigerant | R-407C | R-410A | ||||
| Inlet and outlet port size | Rc1 | Rc1.¼ | ||||
| Outside Dimensions (H x D x W) | mm | 1685 x 905 x 805 | 1825 x 990 x 855 | 1670 x 800 x 1340 | ||
| Product mass | kg | 235 | 285 | 345 | ||